Figure 18
Flow arrangement.
A side
B side
Q
1
/2
Q
1
Q
2
Q
1
Q
2
Q
2
/3
*No number indicates that fl uid passes through
all four holes in the plate.
Drains
T h e r e a r e t h r e e m e t h o d s u s e d f o r d r a i n i n g
SUPERCHANGER units:
1. One pass/one pass (also two pass/two pass with all lower
nozzles, but not shown) units can be drained by opening
the piping to the lower nozzles or by opening drain valves
that can be provided in the fi eld in the connecting piping.
See Figure 19.
2. Multi-pass units may require factory installed drains, i.e., an
additional nozzle in the end frame. These must be factory
installed. See Figure 19.
3. If the number of passes is greater than four as in Figure 20,
the above options require the addition of small holes in
plate corner sections as shown in Figure 22. The amount
of by-pass through these holes is negligible and there is
no possibility of uid intermix. These drain holes in the
element composition diagram (Figure 21) are noted by
,
as the small hole is always placed in the corner without a
passage hole. For example, 1204 is changed to 12
4 if
a drain hole is present. The size and position of the drain
hole is separately specifi ed.
NOTE: On multi-pass units that are sized for a close temperature approach, these drain holes are not provided due to the small amount of
bypassing that occurs. Check the drawing to determine whether drains are present.
Figure 19
One pass—one pass.
B side
A side
Field supplied drain
Factory installed drains
through frame
Plate sequence no.
Plate sequence no.